ולידציה – FSD – System Functions and Facilities

ולידציה – FDS – System Functions and Facilities

 This article was written by Iian Shaya, validation,automation and control expert

.The Function Design Specification (FDS) is part of the validation documentation. In this article I will continue to elaborate the  parts of the FSD of system function and the system facilities

Modes of Operation

This section details all modes of operation for the system, including

Automatic/Manual

Start-up/Shutdown

Overrides

Emergency Shutdown

System Failure and Recovery

Functional Operation

This section divides each of the sequential functions into logical areas (determined by the process), and provide complete description of each function, including

Normal Control Functions – such as normal sequencing, control, etc

Interlocks – details of all interlocks within the function

Alarms – lists of all associated alarms and actions for recovery

Operator Requirements

This section describes the interface between the operator and the detailed function. It is probably the most important to the user during the design phase, as it fully details all the functions to be supplied by the system in order to meet the user's requirements. It must be written clearly and concisely, so that operators and users without technical background can visualize the system to be supplied. Inputs from the user should be clearly detailed so that the operational requirements can be determined

Human/Machine Interface – HMI

This section describes in detail all points of operation, local terminals, remote terminal, message displays, pushbutton stations, etc

Where computerized interfaces are used, such as SCADA or HMI, a list of the screens and the proposed content should be included

Dynamic Attributes – dynamic color changes for status

Display Values – Values to be displayed on screen and resolution- No. of decimal places

Input Devices – Operator interaction devices, mouse, keyboard, touch screen, etc

Alarm and Event Displays

Security – Password Access

System Data

All the data gathered, generated or calculated by the system should be detailed. The detailed data should include

Type

Range

Accuracy/Resolution

Scaling

All the data to be stored should be detailed. This includes historical trend data, alarms and events, taking into consideration the following

Location of data to be stored – fixed disk, floppy disk, etc

Retention period – length of time for the data to be maintained

Data Archive – procedures for backup to removable medium

Data Export – export facilities to other formats, such as Excel, Access, Lotus, etc

System interfaces

This section provides complete details of all inputs and outputs from the control system. When separate I/O schedules are generated, these documents must be referenced in the FDS, or else, the complete schedules must be included in the FDS appendix

For digital and analog I/O, this section should provide details of voltage, current, etc., being specific where interfacing to 3rd party equipment. The signal states should be included as follows

Digital inputs – two states

False or Off

True or On

Analog inputs – detailed range

Detailed communication interfaces between systems should include protocols and formats, and also provide complete details of data to be transferred, paying special attention to 3rd party devices

 This article was written by Iian Shaya, validation,automation and control expert